MODBUS to DP protocol converter MOD-PRO(V3.2)
Product Details
Product name: MODBUS to DP protocol converter MOD-PRO(V3.2)
Features:
Convert instruments, controllers, etc. with MODBUS-RTU protocol interface into products with PROFIBUS-DP slave station protocol interface, and connect these products into PROFIBUS-DP system as PROFIBUS-DP slave stations.
Specifications
- Compliant with PROFIBUS-DP/V0 protocol (JB/T 10308.3-2001: Measurement and Control of Digital Data Communication Industrial Control Systems with Fieldbus Part 3: PROFIBUS Specification).
- Standard PROFIBUS-DP interface, adaptive communication baud rate, maximum communication baud rate 6Mbps.
- The length of PROFIBUS input/output (I/O) can be freely set, the sum of the maximum input length and the maximum output length is 300 bytes, the maximum input length is 240 bytes, and the maximum output length is 240 bytes.
- The DP end has a disconnection detection function.
- The MODBUS end provides three types of communication with other MODBUS devices.
- Universal MODBUS master station: transparent communication with other MODBUS slave stations, strong versatility, support 01, 02, 03, 04, 05, 06, 07, 08, 0B, 0C, 0F, 10H and other MODBUS commands.
- Universal MODBUS slave station: Transparent communication with other MODBUS master stations, strong versatility, support 01, 02, 03, 04, 05, 06, 07, 08, 10H and other MODBUS commands.
- Special type MODBUS master station: Allocate fixed I/O area to all MODBUS slave stations connected to it. Users do not need to understand MODBUS protocol, just follow the instructions to realize communication, support 01H, 02H, 03H, 04H, 05H, 06H, 0FH, 10H and other MODBUS commands.
- MODBUS communication baud rate optional: 300bps, 600bps, 1200bps, 2400bps, 4800bps, 19200bps.
- Power supply: 24VDC±5%, 90mA.
- The communication interface is isolated from the power supply 1000VDC.
- Working environment temperature: -20~70℃.
- Storage temperature: -40~85℃.
- Working environment humidity: ≤90%.
- Protection class: IP20.